Compliant Arc Flash & Shock Equipment Labels

EIN author TerryBecker 400

January 21, 2022

By Terry Becker, P.Eng., CESCP, IEEE Senior Member

When arc flash hazard incident energy calculations are completed the resulting incident energy and arc flash boundary information is placed on the electrical equipment with a detailed arc flash and shock equipment label.  For the last ten (10) years I have reviewed P.Eng. authenticated reports and while on client sites have reviewed installed arc flash & shock equipment labels that were and are NOT compliant!  This has led to the electrical equipment owner being misinformed and their Qualified Electrical Workers also being conditioned to non-compliant information.  As well, restricted energized electrical work tasks that could have been performed are not being performed based on this inaccurate information, which encourages unnecessary downtime and costs organizations money.

The CSA Z462 Workplace electrical safety Standard published it’s 2021, 5th Edition on January 5, 2021.  CSA Z462 has been adopted across all industry sectors from Victoria to Corner Brook.  Even companies that fall under CSA Z462, Clause 1 Scope, Clause 1.2 Application and specifically those that have indicated that the CSA Z462 Standard doesn’t apply to their industry (e.g. marine, u telecommunications, railway and electrical utilities) are using CSA Z462 where it does apply to their facilities.

In the last 10 years, with the CSA Z462 requirement for a Qualified Person to complete and document an Arc Flash Risk Assessment for energized electrical work tasks, P.Eng. Electrical Engineering consultants have been contracted to complete detailed arc flash hazard incident energy analysis studies based on the IEEE 1584 Guide for Performing Arc-Flash Hazard calculations.  The outcome of the P.Eng. authenticated arc flash study report is the provision of detailed arc flash & shock equipment labels.  These labels are then installed on the electrical equipment for which the incident energy calculations were completed.  The Qualified Person then references the arc flash incident energy calculated at the assumed working distance and the arc flash boundary distance to determine “additional protective measures” to apply to reduce risk related to an energized electrical work task they will perform.  The problem historically, which has occurred and is applicable to hundreds of thousands of installed detailed arc flash and shock equipment labels, is that the equipment label specification and information presented is NOT compliant.

The specific information that I have observed which does not meet compliancy is:

  1. Signal pane color and signal pane word used do not comply to the intent of ANSI Z535.
  2. The Signal Pane “Danger” was used for all arc flash & shock equipment labels installed no matter what the incident energy value was.
  3. Wrong color used in the Signal Pane.
  4. Text descriptions used are not consistent with CSA Z462 Clause 3 Definitions e.g. flash hazard boundary, the working distance is not listed as working distance.
  5. The equipment label includes detailed list of arc flash PPE.
  6. The equipment label indicated arc flash PPE with a: HRC #, CAT #, Level “letter,”, or Level “number, 1, 2, 3, 4, 5.”
  7. The footer of the equipment label is not complete.
  8. The footer of the equipment label doesn’t include the specific electrical protective device ID that the incident energy calculation was based on.
  9. The footer of the equipment label doesn’t indicate the location on the electrical equipment where the incident energy applies e.g., load or line side of indicated electrical protective device or the bus.
  10. The size of the equipment label is too small and illegible.
  11. The information was printed on an equipment label that is paper based or not appropriate for placement on electrical equipment in an indoor or outdoor environment.
  12. The equipment label wrongly indicates “Dangerous – No PPE Exists” when the calculated incident energy is greater than 40.0 cal/cm2. This myth was created by the lack of knowledge of P.Eng. Electrical Engineers that potential arc blast pressure released from expansion of air at the point of the abnormal arcing fault correlated to incident energy when it actually correlates to abnormal arcing fault current.  Issued reports also include errors & omissions with respect to interpretation of IEEE 1584 parameter selection.

What can you do?

Get educated, get the facts and hold the P.Eng. Electrical Engineer accountable to substantiate information they have provided in the report and the arc flash & shock equipment labels they recommend.  Ultimately you should take control directly by issuing a detailed Scope of Work and Technical Specification for the arc flash study and an arc flash & shock equipment label specification (see Figure 5).

The individual arc flash & shock equipment label examples in Figures 1 to 4 are compliant to CSA Z462, Clause 4.3.5.7, CSA Z462 Annex Q and ANSI Z535.  As provided, Figure 1 is a typical Warning Signal Pane label when incident energy is less than 140.1 cal/cm2.  Figures 2 and 3 are Warning Signal Pane equipment labels where “Engineering Safety by Design” has been implemented to reduce incident energy (e.g., maintenance mode switch installed, arc flash relay installed).

Figure 1: Standard Arc Flash & Shock Equipment Label, Warning Signal Panel

EIN TB AF Lable 1

 

Figure 2: Arc Flash Relay Installed for Incident Energy Reduction

EIN TB AF 2

 

Figure 3: Maintenance Mode Switch Installed for Incident Energy Reduction

TB AF 3

 

Figure 4: Arc Flash Study Report Results Table Provided

EIN TB AF 4 Copy

 

Figure 5: Danger Signal Pane When Incident Energy Is Greater Than 140.0 cal/cm2

EIN TB AF 5

 

Figure 6: Arc Flash & Shock Equipment Label Infographic

EIN TB AF 6

 

Ensuring that arc flash & shock equipment labels are compliant will ensure that Qualified Electrical Workers correctly interpret the information presented, correctly document their work task’s arc flash risk assessment and shock risk assessment, and don appropriate arc flash and shock PPE validating their residual risk is acceptable.  Ultimately it can save lives and save money!!

As always if you wish to discuss this article please do not hesitate to contact me directly at terry.becker@twbesc.ca.

Terry Becker, P.Eng., CESCP, IEEE Senior Member is the first past Vice-Chair of the CSA Z462 Workplace electrical safety Standard Technical Committee and currently a Voting Member and Clause 4.1 and Annexes Working Group Leader.  Terry is also a Voting Member on the CSA Z463 Maintenance of electrical systems Standard and a Voting Member of the IEEE 1584 Guide for Performing for Arc-Flash Hazard Calculations.   Terry has presented at Conferences and Workshops on electrical safety in Canada, the USA, India and Australia.  Terry is a Professional Engineer in the Provinces of BC, AB, SK, MN and ON.  Terry is an Electrical Safety Specialist, Management Consultant, and can be reached at 1-587-433-3777 or by email terry.becker@twbesc.ca.

Article originally published, Electrical Line Magazine, www.electricalline.com, Month 1/Month 2, Year.

 

Related Articles


Latest Articles

  • ABB’s Care and Modernization Services Breathe Second Life into Legacy Equipment

    ABB’s Care and Modernization Services Breathe Second Life into Legacy Equipment

    April 23, 2024 In today’s world with environmental concerns top of mind, ABB offers sustainable options to extend equipment life through refurbishment and repair—which support a circular economy and reduce landfill footprints. In this context, ABB Canada’s Brampton facility is recognized for offering customized solutions for a growing list of ABB , GE, and non-ABB… Read More…

  • ESA Warns of Unapproved Deprivation Tanks and Electrical Equipment Used by Float Escape Inc. in Ontario

    ESA Warns of Unapproved Deprivation Tanks and Electrical Equipment Used by Float Escape Inc. in Ontario

    April 23, 2024 The Electrical Safety Authority (ESA) is notifying the public about unsafe Deprivation Tanks used for floatation therapy. These products are unapproved and have not been tested for compliance with any Canadian electrical safety standards. Name of Product: Deprivation Tanks (and related various electrical equipment such as pumps, water heaters and control panels). Models: Unknown… Read More…

  • Industrial Projects Lead Non-Residential Construction Intention Gains

    Industrial Projects Lead Non-Residential Construction Intention Gains

    April 22, 2024 Month over month, the total value of building permits in Canada increased 9.3% to $11.8 billion in February. The non-residential sector grew 12.3% to $4.7 billion due to the issuance of several major construction permits, while the residential sector increased 7.4% to $7.1 billion. Ontario (+21.7% to $5.0 billion) led the growth, with gains occurring across all components. On… Read More…

  • Multi-Unit Component Weighs on Investment for February Building Construction Investment

    Multi-Unit Component Weighs on Investment for February Building Construction Investment

    April 22, 2024 Month over month, investment in building construction declined 1.1% to $19.3 billion in February. Investment in the residential sector decreased 1.2% to $13.4 billion, while investment in the non-residential sector fell 0.9% to $6.0 billion. On a constant dollar basis (2017=100), investment in building construction fell 1.2% to $11.9 billion in February, following a flat (+0.0%) movement in the previous… Read More…


Changing Scene

  • Introducing Next Sales and Marketing Inc.

    Introducing Next Sales and Marketing Inc.

    Apr 25, 2024 Dear Valued Business Partners, In an ongoing effort to provide our Partners with the best quality product, service & support, we are excited to announce the appointment of Next Sales and Marketing, as our agent representing Liteline in Atlantic Canada, beginning April 27th, 2024. Next Sales and Marketing caters to a wide… Read More…

  • Lumen Recognized for their Commitment to Sustainable Practices

    Lumen Recognized for their Commitment to Sustainable Practices

    April 23, 2024 Lumen is proud to announce that it has been honored by Ecovadis with a prestigious silver medal. This award recognizes Lumen’s ongoing efforts to integrate sustainable practices into its operations and its unwavering commitment to environmental responsibility. Ecovadis is a globally recognized assessment platform that provides sustainability ratings for companies. It focuses… Read More…

  • CCA Calls for Meaningful Investment as Housing Takes Centre Stage in Budget 2024

    CCA Calls for Meaningful Investment as Housing Takes Centre Stage in Budget 2024

    April 22, 2024 The federal government’s housing strategy is a long-awaited step forward to build more homes, but significantly more investment is needed to address critical infrastructure needs and the housing crisis, says Canada’s construction industry. The federal government’s plan announced in this Budget, as well as actions taken through the 2023 Fall Economic Statement,… Read More…

  • BCCA Response to Federal Budget 2024

    BCCA Response to Federal Budget 2024

    April 22, 2024 BCCA response to the federal budget announcement: The 2024 Federal Budget falls short on a number of policies required to meet the needs of BC’s construction industry, specifically in terms of workforce solutions and infrastructure. Our concern is that demand stimulated by aggressive housing targets and loan programs will surpass the BC… Read More…