It’s Not About the Watts!

Jeff Beare

March 7, 2023

Emergency lighting is a critical aspect of building design that aims to provide illumination in the event of a power outage or other emergency situations. The National Building Code of Canada prescribes specific lighting levels and requirements for emergency lighting systems that are an average of 10 lx with not less than 1 lx at tread. In the past, incandescent lighting sources were commonly used for remote emergency lighting fixtures, with wattage serving as the primary reference point for design selection. However, with the advent of LED technology, the design criteria for selecting appropriate remote heads for emergency lighting systems have shifted towards lumens and spacing. This article discusses the importance of selecting the type of remote head based on lumens and spacing rather than watts in emergency lighting systems.

Importance of Lumens and Spacing

 

The primary design element in emergency lighting is spacing. The greater the spacing provided by remote emergency lighting fixtures, the fewer the number of remotes required to achieve the prescribed lighting levels. This equates to fewer total watts of battery capacity, reducing upfront capital costs, installation costs, and maintenance over the life of the system. Therefore, understanding the basic concept of spacing is crucial for selecting the appropriate remote head for emergency lighting.

Shift in Design Community

 

In the past, the selection of remote heads was based on watts, where higher watts were somewhat equated with better performance. However, in the world of LED, this is no longer true. LED performance is calculated based on efficacy, with lumens per Watt being the unit of measure. Therefore, the selection of the type of remote head should be based on lumens and spacing, with these criteria determining the required wattage. This shift in design criteria necessitates a change in the design community’s approach to selecting the appropriate remote head for emergency lighting systems.

Optics Performance

 

Another critical element to consider when selecting remote heads for emergency lighting systems is the optic performance of the remote manufacturer. The combination of lumen performance and optics results in spacing optimization. Reputable emergency lighting manufacturers publish spacing guides to help with design and remote head selection. Consulting and comparing these guides can help designers quickly realize that a 5 watts remote from Manufacturer A may offer the same or less lumens and spacing than a 3 watts remote from Manufacturer B.

In conclusion, emergency lighting design should focus on selecting the appropriate remote head based on lumens and spacing rather than watts. The greater the spacing provided by remote emergency lighting fixtures, the fewer the number of remotes required, resulting in less total watts of battery capacity, and reduced upfront capital costs, installation costs, and maintenance over the life of the system. The shift in design criteria towards lumens and spacing necessitates a change in the design community’s approach to selecting the appropriate remote head for emergency lighting systems. By considering lumens, spacing, and optics performance, designers can optimize emergency lighting systems to ensure that they meet prescribed lighting levels while minimizing costs.

Jeff Beare is Vice President Emergency Lighting at Stanpro

WWW.stanpro.com

Related Articles


Changing Scene

  • Shine Bright: Call for Speakers Now Open for LEDucation 2025

    LEDucation announces a call for speakers for the 2025 Conference to be held March 18-19 at the New York Hilton Midtown in New York City. Virtual sessions will be offered the prior week, Thursday, March 13th and Friday, March 14th. LEDucation seeks dynamic and engaging speakers who will bring their expertise and unique perspectives particularly… Read More…

  • The DLC’s New Working Group to Collaborate and Advise on Horticultural Lighting Controls

    May 14, 2024 Lighting and controls manufacturers, engineering and design consultants, non-profits, researchers, and indoor cultivators are among stakeholders recently appointed help the DLC accelerate the horticultural lighting industry’s adoption of networked lighting solutions that advance both crop production and energy efficiency. “The controlled environment agriculture industry has grown steadily since the DLC created its… Read More…


Design


New Products

  • Introducing MaxLite’s LS3 Series: Controls-Ready LED Strip Lighting

    May 10, 2024 The new generation of LS Series Linear Strips (LS3 Series) features field-selectable wattages, CCTs and field-installable controls. Offered in three sizes (2′, 4′ and 8′), with each providing nine combinations of colour temperatures and wattages, as well as optional c-Max controls, one product can replace 27 different SKUs for stocking distributors! With… Read More…

  • Discover the Power of SATCO|NUVO’s Hi-Pro A21 High Lumen Lamps

    May 10, 2024 SATCO|NUVO’s LED Hi-Pro A21 Lamps offer ColorQuick convenience ideal for commercial projects. Choose from 2700K/4000K/5000K colour temperatures at installation to achieve the desired atmosphere for the environment. Designed to work in 120V to 277V fixtures, these lamps are compatible with ballast bypass fixtures and are dimmable when used in 120V applications. With… Read More…